Natural Gas, Diesel, Heavy oil, biogas, solar, hot water, exhaust, steam etc.
BROAD chiller can be "three functions in one", cooling/heating/sanitary hot water.
5°C min. for chilled water and 10 °C min. for condenser water inlet.
50~120% for chilled water flow rate. 30~110% for condenser water,
BROAD control panel provides flow vary control signal.
5~115%. Chiller load automatically vary with fan coil load that is PLC controlled.
> Direct fired chiller: 1.42
> Two-stage exhaust chiller/Two-stage hot water chiller/Two-stage steam chiller: 1.50
> Single-stage steam chiller: 0.79
> Single-stage hot water chiller: 0.76
Yes, we have a stock parts warehouse in France.
No, BROAD only focus on the absorption chiller with LiBr solution. No plan to make ammonia absorbers.
Distilled water.
In general, 22 weeks door to door after release and up to 13 weeks in special circumstance.
For hot water driven chiller, Broad offers 2-way or 3-way hot water valve.
For exhaust driven chiller, BROAD offers exhaust valve as optional part.
BROAD offers dry contact, Modbus RTU, BACNET and LonWork.
12 months from commissioning OR 18 months from shipment.
BROAD offers extended warranty up to 30 years..
If limited by access of customers' machine room (or limited by container transportation), split shipment can be chosen. In general, chiller above 1,000 kW will be split into two pieces as main shell and HTG. 3 pipes must be connected at job site.
The standard pressure limit for chilled/heating/cooling water box is 1 Mpa for absorption chiller and 0.8 MPa for Maglev Bearing Oil Free Centrifugal Chiller.
We provide 24/7 monitor service for life time of chiller. An Internet connection is required. If network cable is not available, wireless network also be supported.
Absorption chillers manufacturer