Home > References > Verona, Italy

 

Verona, Italy

An absorption chiller in the trigeneration plant of a hospital

In a hospital in Verona, the BROAD absorption chiller is a key component of the trigeneration plant, which produces electricity, heat and cooling. The plant supplies 7 bar(g) steam for both the absorption chiller and the hospital utilities.

In Italy, hospitals pay a fixed charge based on their contracted electrical capacity, and exceeding it leads to penalties. Driven by steam, the absorption chiller covers peak cooling demand without increasing electricity consumption.

  • Unit type: double-effect steam absorption chiller × 1 unit
  • Cooling capacity: 1,128 kW
  • Heat source: 7 bar(g) steam from the trigeneration plant
  • Cooling water: inlet 29 °C, outlet 34 °C (24 °C wet-bulb temperature)
  • Chilled water: supply 7 °C, return 12 °C
  • Use: hospital air conditioning